随着配电网规模的不断扩大,架空线路绝缘化率的提高,断线故障发生率也随之提高。由于断线故障导致三相电压、电流严重不平衡,危害电气设备和人身安全,影响电力系统供电可靠性。因此,有必要对配电网断线故障定位方法进行研究,在断线故障发生后尽快排查和隔离,减小其造成的危害。本文考虑了分布式电源的影响,对配电网断线故障下分布式电源的负序电压特征进行了分析,在此基础上,根据不同故障位置下分布式电源序电压的差异,提出了一种基于负序电压的配电网断线故障定位方法。仿真结果表明,所提方法能够准确定位断线故障区段,具有较高的可靠性。 With the continuous expansion of the scale of the distribution network, the insulation rate of overhead lines has increased, and the incidence of disconnection faults has also increased. Due to the disconnection fault, the three-phase voltage and current are seriously unbalanced, which endangers electrical equipment and personal safety, and affects the reliability of the power supply of the power system. Therefore, it is necessary to conduct research on the method of locating disconnection faults in the distribution network, and to investigate and isolate them as soon as possible after the disconnection fault occurs, so as to reduce the harm. This paper considers the influence of distributed generations, and analyzes the negative sequence voltage characteristics of distributed generations under the disconnection fault of the distribution network. On this basis, according to the difference in sequence voltage of distributed generations under different fault locations, a method for locating disconnection faults in distribution network based on negative sequence voltage is proposed. The simulation results show that the proposed method can accurately locate the disconnection fault section and has high reliability.
随着配电网规模的不断扩大,架空线路绝缘化率的提高,断线故障发生率也随之提高。由于断线故障导致三相电压、电流严重不平衡,危害电气设备和人身安全,影响电力系统供电可靠性。因此,有必要对配电网断线故障定位方法进行研究,在断线故障发生后尽快排查和隔离,减小其造成的危害。本文考虑了分布式电源的影响,对配电网断线故障下分布式电源的负序电压特征进行了分析,在此基础上,根据不同故障位置下分布式电源序电压的差异,提出了一种基于负序电压的配电网断线故障定位方法。仿真结果表明,所提方法能够准确定位断线故障区段,具有较高的可靠性。
断线故障,配电网,分布式电源,负序电压
Haidong Xu1, Haoning Wang1, Xiaoping He1, Yi Li1, Yang Xiao2, Wenquan He3
1State Grid Chongqing Electric Power Co., Wulong Power Supply Branch Company, Chongqing
2State Key Laboratory of Power Transmission Equipment & System Security and New Technology, Chongqing University, Chongqing
3Chongqing Fengji Intelligent Technology Research Institute Co., Ltd., Chongqing
Received: Jan. 2nd, 2022; accepted: Jan. 15th, 2022; published: Feb. 7th, 2022
With the continuous expansion of the scale of the distribution network, the insulation rate of overhead lines has increased, and the incidence of disconnection faults has also increased. Due to the disconnection fault, the three-phase voltage and current are seriously unbalanced, which endangers electrical equipment and personal safety, and affects the reliability of the power supply of the power system. Therefore, it is necessary to conduct research on the method of locating disconnection faults in the distribution network, and to investigate and isolate them as soon as possible after the disconnection fault occurs, so as to reduce the harm. This paper considers the influence of distributed generations, and analyzes the negative sequence voltage characteristics of distributed generations under the disconnection fault of the distribution network. On this basis, according to the difference in sequence voltage of distributed generations under different fault locations, a method for locating disconnection faults in distribution network based on negative sequence voltage is proposed. The simulation results show that the proposed method can accurately locate the disconnection fault section and has high reliability.
Keywords:Disconnection Fault, Distribution Network, Distributed Generation, Negative Sequence Voltage
Copyright © 2022 by author(s) and Hans Publishers Inc.
This work is licensed under the Creative Commons Attribution International License (CC BY 4.0).
http://creativecommons.org/licenses/by/4.0/
受“重发轻配”的影响,相较于输电网,配电网在自动化水平、继电保护等方面都相对落后。随着近年来城市化进程的加快,用电需求量的加大,配电网规模也在不断扩大 [
按照故障性质的不同,配电网故障类型可分为短路故障和断线故障两种。其中,短路故障主要包括接地故障和相间短路故障,发生率高,通常通过过电流保护和接地故障监测装置等方法切除 [
据此,本文提出了一种基于负序电压的配电网断线故障定位方法。首先将分布式电源等效为受控源,建立了配电网断线故障等效复合序网,进而分析了配电网断线故障下分布式电源机端负序电压的特征。在此基础上,根据分布式电源负序电压的变化特征,提出了一种基于负序电压的配电网断线故障定位方法。该方法以断线故障下分布式电源可能出现的最小负序电压作为故障定位启动值,以分布式电源下游发生断线故障时可能出现的最大负序电压作为故障定位阈值,当所监测到的负序电压大于启动值且大于阈值时,结合配电网中各分布式电源的接入位置情况,确定断线故障区段。仿真结果表明,该方法能够准确定位断线故障区段,且整定计算简单,具有较高的可靠性。所提方法与现有方法相比,利用分布式电源机端电压定位断线故障,无需在馈线上加装其他监测设备,具有较高的可行性。
当配电网发生断线故障时,如图1所示。其中,DG表示分布式电源,f表示断线故障点,Rd表示中性点接地电阻。由于风电、光伏等分布式电源输出特性受控制策略影响,在断线故障下,可以等效为一个受正序电压控制的电流源 [
i D + , f = S D u D + , f (1)
式中, i D + , f 为分布式电源断线故障后输出正序电流; u D + , f 为分布式电源机端正序电压; S D 为分布式电源功率。
图1. 配电网断线故障示意图
当分布式电源至馈线末端之间发生故障时,由于断线故障将使得故障点故障相电流为0,非故障相电压连续,假设故障相为A相,其边界条件为:
{ I ˙ ′ A = 0 Δ U ˙ ′ B = Δ U ˙ ′ C (2)
式中, I ˙ ′ A 为断口处A相电流, Δ U ˙ ′ B 、 Δ U ˙ ′ C 为断口两端B、C相电压。
由对称分量法可得边界条件为:
{ I ˙ ′ A 1 + I ˙ ′ A 2 + I ˙ ′ A 0 = 0 Δ U ˙ ′ A 1 = Δ U ˙ ′ A 2 = Δ U ˙ ′ A 0 (3)
式中, I ˙ ′ A 1 、 I ˙ ′ A 2 、 I ˙ ′ A 0 为断口处正、负、零序电流; Δ U ˙ ′ A 1 、 Δ U ˙ ′ A 2 、 Δ U ˙ ′ A 0 为断口两端电压差。
根据断线点的边界条件以及配电网结构,可以建立对应的等值复合序网图,如图2所示,
图2. 含分布式电源配电网断线故障的等值复合序网图
根据图2所示的等值电路,可以列出对应的基尔霍夫方程:
{ u g = u T + ( u g − u T Z g D + + i D + , f ) [ Z L + + ( Z L − + Z g D − ) ∥ ( Z g D 0 ∥ Z C G N + Z C D N ) ] u D + , f = i D + , f Z D + + ( u g − u T Z g D + + i D + , f ) [ Z L + + ( Z L − + Z g D − ) ∥ ( Z g D 0 ∥ Z C G N + Z C D N ) ] u T = u D + , f − i D + , f Z D + u D − , f = u T ( Z L − + Z g D − ) ∥ ( Z g D 0 ∥ Z C G N + Z C D N ) ( Z L − + Z g D − ) ∥ ( Z g D 0 ∥ Z C G N + Z C D N ) + Z L + ⋅ Z g D − Z g D − + Z L − (4)
式中, u g 为系统电压, Z g D + 、 Z g D − 分别为系统等效阻抗与母线和分布式电源并网点之间线路正、负序阻抗之和; Z D + 、 Z D − 分别为分布式电源升压变电抗与线路正、负序阻抗之和; Z L + 、 Z L − 分别为负荷正、负序阻抗; Z g D 0 为系统等值零序阻抗, Z C G N 为断线点至母线间的等值容抗, Z C D N 为断线点至馈线末端的等值容抗。
对式(4)进行求解,可以得到单相断线故障下,分布式电源机端负序电压:
u D − , f = u T ( Z g D − + Z L − ) ∥ ( Z g D 0 ∥ Z C G N + Z C D N ) + Z L + ⋅ ( Z g D 0 ∥ Z C G N + Z C D N ) Z g D − ( Z g D 0 ∥ Z C G N + Z C D N ) + Z g D − + Z L − (5)
式中, u T 为分布式电源并网点电压。
u T = 2 ( Z g D + + Z D + ) S D − u g + u g 2 + 4 ( Z g D + + Z D + ) S D − − u g + u g 2 + 4 ( Z g D + + Z D + ) S D 2 ( Z g D + + Z D + ) Z D + (6)
根据式(5)和式(6)可以看出,断线点离馈线末端越远,分布式电源机端负序电压越大。并且,当故障发生在分布式电源上游时,由于母线与分布式电源之间存在断线点,分布式电源接入点电压难以依靠母线电压进行有效支撑,此时接入点电压三相不对称度远大于下游断线时的不对称度,因此负序电压也会远大于下游断线时的负序电压。
由上述分析,如果故障点出现在线路末端,并且此时馈线上仅有切入功率最小的分布式电源按其最小功率运行,则分布式电源机端负序电压为发生单相断线故障后的最小值,因此可以将该负序电压作为馈线i单相断线故障定位的启动值 u i , s t 。化简式(4)可知:
u i , s t = H i Z g D − + Z L − + Z L + ⋅ Z g D − (7)
其中,m为切入功率最小的分布式电源。 H i 为:
H i = 2 ( Z g D + Z i , m ) S i , m min − u g + u g 2 + 4 ( Z g D + Z i , m ) S i , m min − − u g + u g 2 + 4 ( Z g D + Z i , m ) S i , m min 2 ( Z g D + Z i , m ) Z i , m (8)
式中, Z i , m 为第m个分布式电源的升压变阻抗; S i , m min 为第m个分布式电源的最小功率。
如果故障点出现在分布式电源并网点,此时分布式电源机端负序电压为该分布式电源至馈线末端发生单相断线故障后负序电压的最大值,可以将该负序电压作为馈线i上第j个分布式电源单相断线故障的定位阈值 U i j , o p t :
U i j , o p t = M i j ( Z g D − + Z L − ) ∥ ( Z g D 0 ∥ Z C G N + Z C D N ) + Z L + ⋅ ( Z g D 0 ∥ Z C G N + Z C D N ) Z g D − ( Z g D 0 ∥ Z C G N + Z C D N ) + Z g D − + Z L − (9)
式中, M i j 为:
M i j = 2 ( Z g D + Z i , j ) S i j t − u g + u g 2 + 4 ( Z g D + Z i , j ) S i j t − − u g + u g 2 + 4 ( Z g D + Z i , j ) S i j t 2 ( Z g D + Z i , j ) Z i , j (10)
式中, Z i , j 为为馈线i上第j个分布式电源的升压变阻抗。
基于分布式电源机端负序电压的配电网单相断线故障定位方法如图3所示,具体定位流程如下。
首先,采集t时刻第i条馈线上各分布式电源的功率 S i j t 和机端负序电压的幅值 U i j − t ,采集t时刻第i条馈线总的负荷正、负序阻抗 Z i , L + t 、 Z i , L − t ,馈线末端的负荷正、负序阻抗 Z i , E + t 、 Z i , E − t 以及每个分布式电源至馈线末端总的负荷正、负序阻抗 Z i j , D + t 、 Z i j , D − t ,其中 i = 1 , 2 , ⋯ , m , j = 1 , 2 , ⋯ , n i ,m为馈线数量, n i 为第i条馈线上的分布式电源数量。
从第i条馈线末端开始,依次比较各分布式电源机端负序电压 U i j − t 与第i条馈线在t时刻的断线定位启动门槛值 U i , s t t 的大小,若第k个分布式电源在t时刻的机端电压负序电压幅值 U i k − t > U i , s t t ,可以判断此时配电网出现了单相断线故障。
此时,分别比较第1个至第k分布式电源机端负序电压幅值与第1个至第k分布式电源的断线故障
定位阈值的大小,若第p个分布式电源的机端负序电压幅值 U i p − t 大于等于第p个分布式电源的断线故障定位阈值 U i p , o p t ,即 U i p − t > U i p , o p t 时,若 p ≥ 2 ,则判定第p个分布式电源至第 p − 1 个分布式电源之间线路发生单相断线故障;若 p = 1 ,则判定母线至第1个分布式电源之间线路发生单相断线故障。
图3. 基于负序电压的配电网断线故障定位方法
本文利用Matlab/Simulink搭建如图1所示的10 kV典型结构配电网模型对所提方法进行验证分析。其中,中性点小电阻Rd为10 Ω。配电网共设有5条馈线,正序参数分别为 r 1 = 0.031 Ω / km , l 1 = 0.096 mH / km , c 1 = 0.338 μF / km ;零序参数分别为 r 0 = 0.234 Ω / km , l 0 = 0.355 mH / km , c 0 = 0.265 μF / km 。馈线1长度为10 km,馈线末端接有负荷5 MW,分布式电源DG1和分布式电源DG2分别接于馈线1的3 km处和8 km处,功率分别为0.5 MW、1 MW。分布式电源升压变阻抗均为1 Ω。
设在 t = 0. 6 s 时馈线1于5 km处发生断线故障,根据式(7)和式(8)可计算得断线故障定位的启动值 u i , s t 为158 V。根据式(9)和式(10),可计算得分布式电源DG1的断线故障定位阈值 U 11 , o p 为162 V,分布式电源DG2的断线故障定位阈值 U 11 , o p 为180 V。仿真结果如图4与图5所示。从图中可以看出,正常运行情况下,分布式电源DG1、DG2的机端负序电压几乎为0。当馈线发生单相断线故障时,分布式电源DG1、DG2的机端负序电压均显著上升。故障稳态下分布式电源DG1机端负序电压为16 V,分布式电源DG1机端负序电压为2346.5 V。结合本文所提方法可知,存在分布式电源负序电压大于启动值158 V,即判断断线故障发生。由于DG1负序电压小于其断线故障定位阈值162 V,因此,故障点位于DG1下游。由于DG2负序电压大于其断线故障定位阈值180 V,因此,故障点位于DG2上游。由此可确定断线故障区段位于馈线1的第1个分布式电源与第2个分布式电源之间。从仿真结果可以看出,本文所提方法能够准确定位断线故障区段,具有较高的可靠性。
图4. 分布式电源DG1机端负序电压
图5. 分布式电源DG2机端负序电压
在双碳目标和分布式电源大规模接入的配电网发展背景之下,本文以含分布式电源配电网为研究对象,分析了含分布式电源配电网断线故障的特征,重点解析分析了分布式电源机端负序电压的表达式。通过本文研究分析表明,断线故障点前后分布式电源的负序电压存在显著差异,该特征能够准确反映故障点位置。因此,根据断线故障后负序电压的变化规律,提出了一种基于分布式电源机端负序电压的断线故障定位方法。该方法通过比较实际分布式电源机端负序电压与所计算的断线故障定位启动值和阈值的大小,来实现故障定位。仿真结果表明,所提方法能够准确定位断线故障区段,且整定计算简单,需要的监测量单一,具有较高的可靠性和可行性。
徐海栋,王浩宁,何小平,李 毅,肖 扬,何文权. 基于负序电压的配电网断线故障定位方法A Method for Locating Disconnected Faults in Distribution Networks Based on Negative Sequence Voltage[J]. 智能电网, 2022, 12(01): 1-8. https://doi.org/10.12677/SG.2022.121001